Water cooled and air cooled chillers anchor central plants in hotels, malls, hospitals, and large offices. Capital cost is large; operating cost is larger across ten to fifteen year life. Efficiency loss is gradual until power bills spike or redundancy fails during a wedding season weekend.
Benchmarking performance
Establish kW per ton at known load and entering wet bulb conditions. Repeat monthly on the same metering point. A five percent drift over two quarters usually traces to fouling, sensor error, or passing three way valves.
- Log chilled water supply and return with calibrated probes.
- For water cooled machines record condenser inlet and outlet.
- Capture VFD hertz on pumps and tower fans.
- Note part load hours versus design; oversize plants hunt and short cycle.
Operational energy levers
- Raise chilled water setpoint within coil capability at AHUs and FCUs.
- Reset condenser water temperature when wet bulb allows.
- Enable chiller staging so only needed machines run.
- Repair leaking control valves that steal chilled water.
- Balance loops; low delta T syndrome wastes pump power and masks coil problems.
Water treatment and mechanical care
Cooling tower scale and biological film insulate condenser tubes silently. Partner chemistry vendors with mechanical tube cleaning windows Essgee schedules during low occupancy periods.
Maintenance calendar
- Monthly: visual inspection, oil sample where applicable, alarm review, vibration listen.
- Quarterly: condenser and evaporator cleaning frequency adjusted to water quality.
- Annual: insulation resistance, safety interlocks, refrigerant leak survey, control calibration.
Retrofit and controls
Primary pump VFD, differential pressure reset, and floating setpoint logic often pay back within two cooling seasons when sub meter data exists. Essgee supports business cases for CFO review.
Request a chiller health audit from Essgee including approach temperature test and written AMC scope for your plant class.